RegO 597FA, 597FB, 597FC and 597FD: Model Comparison

The RegO 597F series comprises high-pressure industrial/commercial pounds-to-pounds regulators. Compare the delivery range and the manufacturer’s published capacity for each exact model; similar connections do not make the four models interchangeable.
Manufacturer-published comparison
| Model | Adjustment range | Capacity test set pressure | Propane vapor capacity | Published kg/hr |
|---|---|---|---|---|
| 597FA | 1–15 PSIG | 10 PSIG | 1,750,000 BTU/hr | 37 |
| 597FB | 10–30 PSIG | 20 PSIG | 3,000,000 BTU/hr | 63 |
| 597FC | 20–45 PSIG | 30 PSIG | 3,500,000 BTU/hr | 74 |
| 597FD | 40–100 PSIG | 40 PSIG | 4,500,000 BTU/hr | 95 |
These figures are transcribed from RegO’s individual model pages checked on 12 November 2026. They are published rating points, not a promise of the same flow at every inlet/outlet condition.
Connections and adjustment
The manufacturer lists 1/4-inch NPT inlet/outlet connections and tee-handle adjustment. Confirm the current model datasheet, connection gender and assembly configuration when preparing an order.
How to use the table
- Identify the required outlet pressure and its reference, such as PSIG.
- Record minimum and maximum available inlet pressure.
- Establish peak demand and the gas service.
- Check the manufacturer’s capacity conditions and operating instructions.
- Confirm downstream pressure limits and required protection.
Where ranges overlap, do not select using capacity alone. Operating conditions and the complete regulator arrangement still need assessment.
Why the kg/hr values differ from some conversions
The table uses the manufacturer’s own published kg/hr figures. An energy conversion on a different heating-value basis can produce another number, but that is not a new tested regulator rating.
Quotation checklist
Send the complete model, gas, inlet/outlet conditions, required duty, connection details and quantity. For a replacement, include the nameplate photograph. Qualified personnel must confirm settings and installation; this comparison is not an adjustment procedure.
Related guides
- First Stage Regulators: The Key to Safe, Efficient LPG Systems
- Commercial and Industrial LPG Systems: Complete Guide
Equipment and enquiries
Request a gas-equipment quotation with the application, model reference where known, operating requirements, quantity and delivery location.
Sources and further technical reading
- RegO 597FA current model data
- RegO 597FB current model data
- RegO 597FC current model data
- RegO 597FD current model data
General equipment-selection information. Confirm the exact model documentation and applicable project requirements with qualified personnel before selection, installation or adjustment.