An automatic gas shut-off valve closes a gas path when its operating mechanism or control system calls for isolation. An electrically operated valve normally needs a compatible external signal; it does not necessarily detect a gas leak itself.

Three functions that are often confused

Device/function What triggers it? What to verify
Electrically operated shut-off A compatible electrical command or power condition. Voltage, operating logic, reset behavior and controller compatibility.
Pressure-operated slam-shut The monitored pressure reaches its specified trip condition. Pressure sensing, trip range and reset requirements.
Excess-flow protection Flow reaches the device’s specified operating condition. Rated flow and the installation conditions required for operation.

These functions are not interchangeable. In particular, excess-flow protection may not operate for a small leak, and a pressure trip is not a gas-concentration measurement.

How detection can initiate isolation

A suitable gas detector sends information to the specified controller. The controller then operates alarms and the shut-off output according to the approved logic. The selected valve must be compatible with that output and the required safe state.

Normally closed and reset behavior

Check what happens on power failure, gas alarm and restoration of power. “Normally closed” does not, by itself, describe every reset or reopening condition. The manufacturer’s instructions must establish whether manual intervention is needed.

Selection checklist

  • Gas, phase, temperature and pressure range.
  • Required flow and permitted pressure loss.
  • Connection standard, size and orientation.
  • Supply voltage, power and control interface.
  • Trip, power-loss and reset behavior.
  • Environmental rating and required approvals.

Testing and restart

Qualified personnel should verify the detector, controller and valve together under the approved procedure. After a trip, investigate the cause before any authorized restart. Do not bypass a safety device or repeatedly reset an unresolved alarm.

If a leak is suspected, follow the site emergency plan and leave the affected area. An equipment enquiry is for planned selection and replacement, not emergency assistance.